Next mtg to discuss EE HV dist systemFrom: Dave Cockerill Sent: 12 March 2007 09:38 To: Dave Cockerill; 'Claire H Shepherd-Themistocleous'; Bob Brown; Martin Torbet; Barbara Camanzi; Ken Bell; 'R.Stephenson@rl.ac.uk' Subject: Minutes EE HV dist system, 1 Feb 2007 Importance: High Minutes EE HV dist system, 1 Feb 2007 Present Martin, Bob, Ken, Barbara, Dave Martin - System based on 1 input card + 1 control card + 2 output cards => serves 24 supercrystals Box 3U high into 19" rack Assume air flow goes around box 6 o/p cards per crate, up to 5 or 6 i/p cards 1 crate/quad for standard SCs = 2 crates per Dee 1 crate for the peripherals = 1 crate per Dee 3 crates per Dee, 6 crates per end + 1 box for low voltage power supply and HV breakout ACTIONS * add warning leds, front and back for HV and LV * i/p cards, one led per fault line Define: "Fault output", out of crate "Ext-trip" "Ext-reset" * Crate trip - clamps all cards down until an external reset * 1 reset button on crate, one on rack? * Overvoltage V(limit) = 1500V, fixed by resistors * Lemo for logic and outputs at low voltage * Output current monitor = log preamp, 5nA resolution * i(over) set at 450 microamp WORK PROGRAMME layout of cards completed by end April 07 Mechanical design of connectors Test and acceptance procedures, particularly for the output card (ringing through) Dave Cockerill 12.3.2007